General |
|
|
|
|
|
|
Certifications |
CE, FCC class A |
|
|
|
|
Dimensions (W x H x D) |
30 x 139 x 100 mm |
|
|
|
|
Enclosure |
ABS+PC |
|
|
|
|
|
Weight |
170 g |
|
|
|
|
|
Power Consumption |
4 W @ 24 VDC (APAX-5017) |
|
|
|
(typical) |
3.5 W @ 24 VDC (APAX-5018) |
|
|
|
|
|
|
|
|
|
|
Analog Input |
|
|
|
|
|
|
Channels |
12 (Differential) |
|
|
|
|
Input Type |
V, mV, mA (APAX-5017) |
|
|
|
|
V, mV, mA, Thermocouple (APAX-5018) |
|
|
Input Impedance |
Voltage: >10 MW (APAX-5017), >1 MW (APAX-5018) |
|
Current: 120W (Current) |
|
|
|
Voltage/Current Range |
±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 |
|
mA, 4 ~ 20 mA (APAX-5017) |
|
|
|
|
±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V, ±20 mA, |
|
0 ~ 20 mA, 4 ~ 20 mA (APAX-5018) |
|
|
Temperature Range |
Type J (-210 ~ 1200° C), Type K (-270 ~ 1372° C), |
(APAX-5018 only) |
Type T (-270 ~ 400° C), Type E (-270 ~ 1000° C), |
|
Type R (0 ~ 1768° C), Type S (0 ~ 1768° C), |
|
Type B (300 ~ 1820° C) |
|
|
|
Configure Different Range for Each Channel |
|
|
|
|
Resolution |
16-bit with accuracy ±0.1% or better of Full Scale Range |
|
(Voltage), ±0.2% or better of Full Scale Range(Current) |
Note: Refer to manual for Thermocouple accuracy |
|
|
|
Sampling Rate |
12 samples/second (total) |
|
|
|
Noise Rejection |
Hardware Filter (50/60 Hz) |
|
|
|
Wire Burn-out Detection |
APAX-5017: Yes (4 ~ 20 mA only) |
|
|
|
APAX-5018: Yes (4 ~ 20 mA and Thermocouple) |
|
Common Mode Voltage |
200 VDC |
|
|
|
|
|
|
|
|
|
|
|
|
Protection |
|
|
|
|
|
|
2,500 VDC Isolation Between Channels and Backplane |
|
|
|
Over Voltage Protection |
|
|
|
|
|
|
|
|
|
|
|
|
|
Environment |
|
|
|
|
|
|
Operating Temperature |
-10 ~ 60° C (when mounted vertically) |
|
Storage Temperature |
-40 ~ 70° C |
|
|
|
|
Relative Humidity |
5 ~ 95% (non-condensing) |
|
|
|